block-0

Low voltage distribution line

block-1

Description of the distribution line

block-2

The distribution network will be overhead, low voltage (400 Vac with 3 phases + neutral) with a nominal frequency of 50 Hz and will consist of the following elements.

block-3

Three-phase cabletwisted aluminumwith neutral carrier, including single-phase public lighting.

block-4
来源图片 / 图纸
asset-7adc280fdec942b7
block-5

Wooden distribution line poles.

block-6

Accessories for the distribution line, including suspension, anchoring and tensioning clamps, insulation piercing branch connectors, splicing sleeves, guy wires, etc.

block-7

Grounding system with a TT type neutral system, both at several points of the distribution line and at each user's premises.

block-8

LED street lighting.

block-9

The distribution line will be equipped with at least five disconnectors, ensuring efficient energy management in critical situations by allowing the disconnection of certain parts of the network. This installation will prioritize the energy supply to the health center and other healthcare facilities.

block-10

Low-voltage connections for users:

block-11

Network connection, including:

block-12

2x16 mm2 Alu connection cables for single-phase users.

block-13

Wooden receiving post, installed next to the user's wall. The existing fireplaces are not strong enough to withstand the mechanical forces of the connection. Therefore, it is preferable to connect the user via an additional receiving pole.

block-14

Individual circuit breaker installed on the walloutside the home.

block-15

Individual derivation, including:

block-16

Wiring between the individual circuit breaker and the delivery point, located inside the home, having passed through the wall.

block-17

Single-phase prepayment electricity meter.Some meters, dedicated to special users for whom the standard meter is not suitable (drinking water supply, welding workshops, grain mills, etc.), will have to be defined by the developer on a case-by-case basis, taking into consideration the specific characteristics of the user (three-phase, power demand, current and energy, etc.).

block-18

Individual protective equipment box.The internal protection boxes for specific users such as drinking water supply (DWS) or welding workshops must be arranged on a case-by-case basis with the user concerned and in accordance with the relevant quality and safety standards associated.

block-19

Individual grounding.

block-20

Indoor installation, including

block-21

Sockets, switches, LEDs and all necessary wiring and accessories.

block-22

Any other equipment and materials necessary for the proper and safe operation of the distribution line.

block-23

The distribution line and branches must be designed and constructed according to the standards used by the national network manager, or NF C 11-201 and NF C 15-100.

block-24

Component requirements

block-25

The bidder is required to complete all technical specification tables provided in this section, also attached in Excel format as Appendix F – Technical Specification Table. The bidder will indicate whether a requirement is fully compliant (FC), partially compliant (PC), or non-compliant (NC). The bidder will provide an explanatory note if the requirement is PC or NC. The bidder will indicate which document (and which section of the document, if applicable) provides evidence for each requested requirement. The supporting document may be, for example, a technical data sheet, a design drawing prepared by the bidder, a specific section of the bidder's design report, or other documents.

block-26

All critical requirements (EC) specified in the last column must be met to ensure that the bulk of the offer complies with these minimum technical requirements. Non-critical requirements (ENC) are recommended, but not mandatory.

block-27

Distribution line poles

block-28
IDSpecificationValues/StandardsCritical requirement (CR) or Non-critical requirement (NCR)
LD-POT-1Applicable standardsNF EN 14229: Wooden poles for overhead linesEC
LD-POT-2MaterialDrinkEC
LD-POT-3Height9 mEC
LD-POT-4Nominal effort255 daN for all poles which are intended to suspend the bundle of twisted cable in alignment.

550 daN for all poles located at an angle (change of direction of the line), branch or stop of line, and which are subject to one or more cable anchorages (either single or double).
EC
LD-POT-5Permissible fuelsPine, Fir, Spruce, Larch. Eucalyptus is prohibited.EC
LD-POT-6Wood preservation treatmentAccording to NF EN 599-1 and NF EN 351-1, creosote treatment is prohibited.EC
LD-POT-7MarkingEach post must bear the following inscriptions in indelible characters: - Supplier's name - Impregnation process designated by its reference letter - Year of manufacture - Height of the post in meters - Nominal force - Manufacturing order number if applicable. The marking support is placed on the shaft of the post, 3.50m from the base.EC
LD-POT-8Type test reportThe manufacturer must provide a type test report. The tests will be carried out according to the standards in force, and concern both: - the quality of the supplies and the proper execution of the processing operations, - the dimensions, straightness and quality of the wood, - mechanical resistance tests (yield strength and breaking strength).EC
block-29

User reception posts

block-30
IDSpecificationValues/StandardsCritical requirement (CR) or Non-critical requirement (NCR)
LD-POT-REC-1Applicable standardsNF EN 14229: Wooden poles for overhead linesEC
LD-POT-REC-2Height5 mEC
LD-POT-REC-3Nominal effort550 daNEC
LD-POT-REC-4Permissible fuelsPine, Fir, Spruce, Larch. Eucalyptus is prohibited.EC
LD-POT-REC-5Wood preservation treatmentAccording to NF EN 599-1 and NF EN 351-1, creosote treatment is prohibited.EC
LD-POT-REC-6MarkingEach post must bear the following inscriptions in indelible characters: - Supplier's name - Impregnation process designated by its reference letter - Year of manufacture - Height of the post in meters - Nominal force - Manufacturing order number if applicable. The marking support is placed on the shaft of the post, 3.50m from the base.EC
LD-POT-REC-7Type test reportThe manufacturer must provide a type test report. The tests will be carried out according to the standards in force, and concern both: - the quality of the supplies and the proper execution of the processing operations, - the dimensions, straightness and quality of the wood, - mechanical resistance tests (yield strength and breaking strength).EC
block-31

Cables

block-32
IDSpecificationValue/Standards/RequirementCritical requirement (CR) or Non-critical requirement (NCR)
Three-phase distribution cables with public lighting
LD-C-1Applicable standardsNF C 33-209EC
LD-C-2Cable TypePre-assembled twisted conductors in a bundle consisting of a neutral carrier made of aluminium alloy (Almelec) around which the phase conductors of the distribution and public lighting line are twisted.EC
LD-C-3MaterialThe phase conductors are made of aluminium and the neutral is made of Almelec.EC
LD-C-4Cable size.3*35+54.6+16mm²3*70+54.6+16mm²EC
LD-C-5phase conductor typeCircular cross-section, stranded and compacted aluminumEC
LD-C-6Neutral conductor typeCircular cross-section, twisted and must be made of uncompacted aluminum alloy.EC
LD-C-7Insulation.The conductors must be insulated with cross-linked polyethylene (CRP).EC
LD-C-8FacilityAirEC
LD-C-9Nominal voltage.0.6/1 KVEC
LD-C-10Manufacturer
LD-C-11Model
Single-phase user connection cable
LD-C-12Applicable standardsNF C 33-209EC
LD-C-13Cable TypeTwistedEC
LD-C-14Conductive material.AluminumEC
LD-C-15Cable size.2x16 mm2EC
LD-C-16Insulation.The conductors must be insulated with cross-linked polyethylene (CRP).EC
LD-C-17FacilityAirEC
LD-C-18Nominal voltage.0.6/1 KVEC
LD-C-19Manufacturer
LD-C-20Model
Three-phase user connection cable
LD-C-21Applicable standardsNF C 33-209EC
LD-C-22Cable TypeTwistedEC
LD-C-22Conductive material.AluminumEC
LD-C-23Cable size.4x25 mm2EC
LD-C-24Insulation.The conductors must be insulated with cross-linked polyethylene (CRP).EC
LD-C-25FacilityAirEC
LD-C-26Nominal voltage.0.6/1 KVEC
LD-C-27Manufacturer
LD-C-28Model
block-33

Accessories

block-34
IDSpecificationValue/Standards/RequirementCritical requirement (CR) or Non-critical requirement (NCR)
Main line
LD-ACC-1HardwareThey must be effectively protected against corrosionEC
LD-ACC-2Insulation.The parts in direct contact are made of insulating material and their insulation voltage must be at least 6 kV.EC
LD-ACC-3Anchor clampsThey must not break or allow permanent slippage of the conductor for a force less than 1500 daN for a carrier of 54.6 mm2.

Applicable standards: NF C 33-041 and NF C 33-042
EC
LD-ACC-4Neutral carrier suspension clampsThey must not allow permanent slippage of the conductor for a force less than 30 daN, in the direction of the line, moreover, they must be calculated to withstand the mechanical tension of the cable according to the assumption considered.
Applicable standards: NF C 33-040
EC
LD-ACC-5Joint sleeves and end lugsHexagonal taper. Applicable standards: NF C 33-021EC
LD-ACC-6Insulation of joint sleeves and branch fittingsSame insulation characteristics as the cable.EC
User connections
LD-ACC-7Hardware and accessoriesThe parts in direct contact with the cable insulation are made of insulating material and their insulation voltage must be at least 4 kV for one minute.EC
LD-ACC-8Branch connectorsInsulation perforation. Applicable standard: NF C 33-020EC
block-35

Public lighting

block-36
IDSpecificationValue/Standards/RequirementCritical requirement (CR) or Non-critical requirement (NCR)
LP-1Type of lightingSingle body with two independent volumes: one for electronic equipment and the other for the LED type lamp optical group.EC
LP-2Lamp power≥34 WEC
LP-3LED Output≥ 110 Lm/WEC
LP-4Lifetime50,000 hEC
LP-5Color temperature5,000 KEC
LP-6Lighting fixture materialsPolyester or AluminumEC
LP-7IP protection rating≥ IP 66EC
block-37

Energy meters

block-38
IDSpecificationValue/Standards/RequirementCritical requirement (CR) or Non-critical requirement (NCR)
CM-1Number of phasesSingle-phaseEC
CM-2Nominal voltage.230 VEC
CM-3Tension tolerance80%...110% of rated voltageEC
CM-4Nominal frequency.50 HzEC
CM-5Frequency tolerance90%...110% of the nominal frequencyEC
CM-6Accuracy of energy measurement.Active energy: Class I
Reactive energy: Class II
EC
CM-7Base current Ib≥ 5 AEC
CM-8Maximum current.≥ 40 AEC
CM-9Starting current.≤ 20 mAEC
CM-10Self-consumption≤ 3 WEC
CM-11IP rating≥ IP53EC
CM-12Operating temperature range0-50CEC
CM-13Payment typePrepaid and postpaid features.EC
CM-14Type of rechargeExternal rechargeable card, tokens, or automatically via remote managementEC
CM-15It is possible to program different plans per user (i.e., variation of the energy/power limit) and with a minimum of 6 different consumption levels (6 different user types).IncludedEC
CM-16Data storage capacity for at least one month in case of power outage (internal battery to retain memory)IncludedEC
CM-17InterfaceLCD screen with LED indicators that show: - Remaining energy display (energy balance, credit level…) - Current power - AlarmsEC
CM-18Automatic disconnection.In case of non-payment, sabotage, exceeding the power limit (for current), and exceeding the daily energy allocation.EC
CM-19License management platformIncluded for > 3 years, including: - client mini-network management software - client database management - account and transaction recording - individual flat-rate configuration for clients - ensuring data security and encryption by allowing different access levelsEC
CM-20Theft protectionThe upstream terminals will be protected and sealed against theft.EC
CM-21RelayAuxiliary relay for disconnecting non-essential loads.ENC
block-39

Indoor installation protection box

block-40
IDSpecificationValue/Standards/RequirementCritical requirement (CR) or Non-critical requirement (NCR)
BPII-1IP rating≥IP54EC
BPII-2InsulationClass IIEC
BPII-3Protective EquipmentSingle-phase general residual current circuit breaker (nominal voltage 230V, nominal current 25A, sensitivity 30 mA, 2 poles);

Single-phase thermal-magnetic switch for sockets (rated voltage 230V, rated current 10A, 2 poles);

Single-phase thermal-magnetic switch for lighting lines (rated voltage 230V, rated current 6A, 2 poles);
EC